Alarm List

The following table summarizes all of the possible alarms that can be generated by the Pinnacle 20|20 Control System:

ID 0-49

ID
Name
Type
Cause

2

Linear Limit Fire Alarm

C

Linear Limits Circuit is Open - One of the LLC switches has opened due to high temperature.

3

High Gas Pressure Fault

C

High gas pressure detected in the gas train.

4

Emergency Stop Depressed

C

Emergency Stop depressed.

10

Motor Overload(s)

C

Overload has been detected for one of the motors, check the motor circuit protector or soft starter if equipped.

11

Blowers Tri-Start Auxiliary

A

One of the two contactors A or B has experienced a fault condition.

16

Grain Fill Timeout

B

Infeed grain fill is insufficient to maintain grain level.

24

Low Gas Pressure

B

Low gas/fuel pressure detected in the gas/fuel train.

26

Discharge Level

B

The discharge level switch is open due to a possible overload of grain or a blocked discharge takeaway system.

27

Customer Takeaway Fault

B

The customer takeaway equipment has failed or is not on, check customer takeaway equipment status contacts.

28

Discharge Jam - Proximity Switch

B

The Discharge metering system has possibly stopped running because the proximity sensor is not detecting rotation.

35

Mid Grain Band

A

The mid-grain temperature has exceeded or dropped below the mid-grain band alarm setpoint for a duration of 30 seconds.

36

Mid-Grain Band Delay

B

The mid-grain temperature has exceeded or dropped below the mid-grain band alarm setpoint for the duration of the mid-grain band delay.

37

Mid-Grain Temperature Probe 1

A

Mid-grain temperature probe #1 has failed or become disconnected.

38

Mid-Grain Temperature Probe 2

A

Mid-grain temperature probe #2 has failed or become disconnected.

49

Plenum Door(s)

C

An open plenum door has been detected with the control power on.

ID 50-99

ID
Name
Type
Cause

50

Customer E-Stop

C

Customer E-Stop Activated.

51

Plenum 1 Low Temperature

B

The temperature in plenum #1 has dropped below the low temperature setpoint.

52

Plenum 2 Low Temperature

B

The temperature in plenum #2 has dropped below the low temperature setpoint.

53

Plenum 3 Low Temperature

B

The temperature in plenum #3 has dropped below the low temperature setpoint.

54

Plenum 4 Low Temperature

B

The temperature in plenum #4 has dropped below the low temperature setpoint.

55

Plenum 5 Low Temperature

B

The temperature in plenum #5 has dropped below the low temperature setpoint.

56

Plenum 6 Low Temperature

B

The temperature in plenum #6 has dropped below the low temperature setpoint.

57

Plenum 7 Low Temperature

B

The temperature in plenum #7 has dropped below the low temperature setpoint.

58

Plenum 8 Low Temperature

B

The temperature in plenum #8 has dropped below the low temperature setpoint.

61

Plenum 1 High Temperature

C

The temperature in plenum #1 has exceeded the high temperature setpoint.

62

Plenum 2 High Temperature

C

The temperature in plenum #2 has exceeded the high temperature setpoint.

63

Plenum 3 High Temperature

C

The temperature in plenum #3 has exceeded the high temperature setpoint.

64

Plenum 4 High Temperature

C

The temperature in plenum #4 has exceeded the high temperature setpoint.

65

Plenum 5 High Temperature

C

The temperature in plenum #5 has exceeded the high temperature setpoint.

66

Plenum 6 High Temperature

C

The temperature in plenum #6 has exceeded the high temperature setpoint.

67

Plenum 7 High Temperature

C

The temperature in plenum #7 has exceeded the high temperature setpoint.

68

Plenum 8 High Temperature

C

The temperature in plenum #8 has exceeded the high temperature setpoint.

75

Infeed Moisture Sensor Signal Missing

A

The infeed sensor signal has dropped to below 0.5VDC and is probably disconnected.

76

Infeed Moisture Sensor Signal Too High

A

The infeed sensor signal has exceeded 9.5VDC and is probably too wet or faulty.

77

Discharge Moisture Sensor Signal Missing

A

The discharge sensor signal has dropped to below 0.5VDC and is probably disconnected.

78

Discharge Moisture Sensor Signal Too High

A

The discharge sensor signal has exceeded 9.5VDC and is probably too wet or faulty.

79

Fill 1 Equipment Fault

B

Fill 1 Equipment Status signal failed to close after signal to operate fill equipment.

80

Fill 2 (Cleanout) Equipment Fault

B

Fill 2 Equipment Status signal (Level Auger) Failed to close after signal to operate fill cleanout equipment.

ID 100-149

ID
Name
Type
Cause

100

Dryer Master Communications

A

The Dryer Master system board is not responding; check: (A) - Dryer Master board not powered up; (B) - Communications between PLC and Dryer Master board; (C) - Dryer Master software stopped.

111

High Discharge Moisture

A

The system has experienced high discharge moisture.

113

High Discharge Temperature

A

The system has experienced high discharge temperature.

114

Critical High Discharge Temperature

B

The system has experienced critical high discharge temperature.

115

Low Discharge Moisture

A

The system has experienced low discharge moisture.

116

Critical Low Discharge Moisture

B

The system has experienced critical low discharge moisture.

117

Low Discharge Temperature

A

The system has experienced low discharge temperature.

118

Critical Low Discharge Temperature

B

The system has experienced critical low discharge temperature.

121

High Infeed Moisture

A

The system has experienced high infeed moisture.

122

Critical High Infeed Moisture

B

The system has experienced critical high infeed moisture.

123

High Infeed Temperature

A

The system has experienced high infeed temperature.

124

Critical High Infeed Temperature

B

The system has experienced critical high infeed temperature.

125

Low Infeed Moisture

A

The system has experienced low infeed moisture.

126

Critical Low Infeed Moisture

B

The system has experienced critical low infeed moisture.

127

Low Infeed Temperature

A

The system has experienced low infeed temperature.

128

Critical Low Infeed Temperature

B

The system has experienced critical low infeed temperature.

131

High Plenum Temperature

A

The system has experienced high plenum temperature.

132

Critical High Plenum Temperature

B

The system has experienced critical high plenum temperature.

133

Low Plenum Temperature

A

The system has experienced low plenum temperature.

134

Critical Low Plenum Temperature

A

The system has experienced critical low plenum temperature.

135

AccuDry Suspended

B

The system is suspended due to: a. Rate out of range, b. Moisture sensor signal missing, or c. Drying temperature out of range.

141

High Discharge Speed

A

The system has experienced high discharge speed.

142

Critical High Discharge Speed

B

The system has experienced critical high discharge speed.

143

Low Discharge Speed

A

The system has experienced low discharge speed.

144

Critical Low Discharge Speed

B

The system has experienced critical low discharge speed.

145

Plenum 1 High Limit Switch

C

Burner #1 high temperature switch has been activated.

146

Plenum 2 High Limit Switch

C

Burner #2 high temperature switch has been activated.

147

Plenum 3 High Limit Switch

C

Burner #3 high temperature switch has been activated.

148

Plenum 4 High Limit Switch

C

Burner #4 high temperature switch has been activated.

149

Plenum 5 High Limit Switch

C

Burner #5 high temperature switch has been activated.

ID 150-199

ID
Name
Type
Cause

150

Plenum 6 High Limit Switch

C

Burner #6 high temperature switch has been activated.

151

Plenum 7 High Limit Switch

C

Burner #7 high temperature switch has been activated.

152

Plenum 8 High Limit Switch

C

Burner #8 high temperature switch has been activated.

153

Blower 1 Motor Starter

A

Blower #1 motor starter has experienced a fault condition.

154

Blower 2 Motor Starter

A

Blower #2 motor starter has experienced a fault condition.

155

Blower 3 Motor Starter

A

Blower #3 motor starter has experienced a fault condition.

156

Blower 4 Motor Starter

A

Blower #4 motor starter has experienced a fault condition.

157

Blower 5 Motor Starter

A

Blower #5 motor starter has experienced a fault condition.

158

Blower 6 Motor Starter

A

Blower #6 motor starter has experienced a fault condition.

159

Blower 7 Motor Starter

A

Blower #7 motor starter has experienced a fault condition.

160

Blower 8 Motor Starter

A

Blower #8 motor starter has experienced a fault condition.

161

Blower 1 Air Pressure

B

Blower #1 is not providing adequate pressure for burner operation.

162

Blower 2 Air Pressure

B

Blower #2 is not providing adequate pressure for burner operation.

163

Blower 3 Air Pressure

B

Blower #3 is not providing adequate pressure for burner operation.

164

Blower 4 Air Pressure

B

Blower #4 is not providing adequate pressure for burner operation.

165

Blower 5 Air Pressure

B

Blower #5 is not providing adequate pressure for burner operation.

166

Blower 6 Air Pressure

B

Blower #6 is not providing adequate pressure for burner operation.

167

Blower 7 Air Pressure

B

Blower #7 is not providing adequate pressure for burner operation.

168

Blower 8 Air Pressure

B

Blower #8 is not providing adequate pressure for burner operation.

169

Blower 1 Air Pressure Switch

A

Blower #1 air pressure switch is indicating air pressure when the blower is not operating.

170

Blower 2 Air Pressure Switch

A

Blower #2 air pressure switch is indicating air pressure when the blower is not operating.

171

Blower 3 Air Pressure Switch

A

Blower #3 air pressure switch is indicating air pressure when the blower is not operating.

172

Blower 4 Air Pressure Switch

A

Blower #4 air pressure switch is indicating air pressure when the blower is not operating.

173

Blower 5 Air Pressure Switch

A

Blower #5 air pressure switch is indicating air pressure when the blower is not operating.

174

Blower 6 Air Pressure Switch

A

Blower #6 air pressure switch is indicating air pressure when the blower is not operating.

175

Blower 7 Air Pressure Switch

A

Blower #7 air pressure switch is indicating air pressure when the blower is not operating.

176

Blower 8 Air Pressure Switch

A

Blower #8 air pressure switch is indicating air pressure when the blower is not operating.

177

Burner 1 Ignition Failure

A

Burner #1 has not been able to maintan an adequate flame signal for dryer operation.

178

Burner 2 Ignition Failure

A

Burner #2 has not been able to maintan an adequate flame signal for dryer operation.

179

Burner 3 Ignition Failure

A

Burner #3 has not been able to maintan an adequate flame signal for dryer operation.

180

Burner 4 Ignition Failure

A

Burner #4 has not been able to maintan an adequate flame signal for dryer operation.

181

Burner 5 Ignition Failure

A

Burner #5 has not been able to maintan an adequate flame signal for dryer operation.

182

Burner 6 Ignition Failure

A

Burner #6 has not been able to maintan an adequate flame signal for dryer operation.

183

Burner 7 Ignition Failure

A

Burner #7 has not been able to maintan an adequate flame signal for dryer operation.

184

Burner 8 Ignition Failure

A

Burner #8 has not been able to maintan an adequate flame signal for dryer operation.

185

Burner 1 False Flame

C

The flame sensing system has detected the presence of a flame with burner #1 off.

186

Burner 2 False Flame

C

The flame sensing system has detected the presence of a flame with burner #2 off.

187

Burner 3 False Flame

C

The flame sensing system has detected the presence of a flame with burner #3 off.

188

Burner 4 False Flame

C

The flame sensing system has detected the presence of a flame with burner #4 off.

189

Burner 5 False Flame

C

The flame sensing system has detected the presence of a flame with burner #5 off.

190

Burner 6 False Flame

C

The flame sensing system has detected the presence of a flame with burner #6 off.

191

Burner 7 False Flame

C

The flame sensing system has detected the presence of a flame with burner #7 off.

192

Burner 8 False Flame

C

The flame sensing system has detected the presence of a flame with burner #8 off.

193

Plenum #1 Temperature RTD Failure

B

Plenum #1 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

194

Plenum #2 Temperature RTD Failure

B

Plenum #2 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

195

Plenum #3 Temperature RTD Failure

B

Plenum #3 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

196

Plenum #4 Temperature RTD Failure

B

Plenum #4 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

197

Plenum #5 Temperature RTD Failure

B

Plenum #5 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

198

Plenum #6 Temperature RTD Failure

B

Plenum #6 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

199

Plenum #7 Temperature RTD Failure

B

Plenum #7 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

ID 200-249

ID
Name
Type
Cause

200

Plenum #8 Temperature RTD Failure

B

Plenum #8 RTD input module on the PLC has detected a fault. Either the temperature transmitter or the RTD has failed.

201

Burner 1 Lost Flame

B

Burner #1 successfully ignited, but was unable to maintain a sufficient flame.

202

Burner 2 Lost Flame

B

Burner #2 successfully ignited, but was unable to maintain a sufficient flame.

203

Burner 3 Lost Flame

B

Burner #3 successfully ignited, but was unable to maintain a sufficient flame.

204

Burner 4 Lost Flame

B

Burner #4 successfully ignited, but was unable to maintain a sufficient flame.

205

Burner 5 Lost Flame

B

Burner #5 successfully ignited, but was unable to maintain a sufficient flame.

206

Burner 6 Lost Flame

B

Burner #6 successfully ignited, but was unable to maintain a sufficient flame.

207

Burner 7 Lost Flame

B

Burner #7 successfully ignited, but was unable to maintain a sufficient flame.

208

Burner 8 Lost Flame

B

Burner #8 successfully ignited, but was unable to maintain a sufficient flame.

217

Safety Relay Failure

C

The Safety Relay failed to latch. Check the safety relay circuit is complete.

218

Cool Down Stopped

B

Cooldown Mode stop via HMI pushbutton.