LogoLogo
Dryer Operations
Dryer Operations
  • Dryer Operations
    • Applicability
    • Introduction
    • Warranty
    • CSA 3.8 2021
    • Specifications
      • Delta Series
      • Fusion Series
      • ECO Series
      • Legacy Series
      • Modular Tower Series
      • Commercial Tower Series
    • Equipment Overview
      • Main Dryer Components
      • High Voltage Cabinet
      • Low Voltage Cabinet
      • Pinnacle 20|20 Remote Cabinet
      • Customer Equipment Cabinet
      • Burner Control Cabinet
      • Discharge Moisture Sampler
      • Gas Train
      • Burner
    • Operating Procedures
      • Component Adjustments
      • Air Pressure Switch
      • High Limit Switch
      • VFD (Parameters)
        • Profile & Mixed-Flow Models
        • Modular Towers (208/230/460V)
        • Modular Towers (380/575V)
        • Commercial Towers (208/230/460V)
      • Soft Start (Parameters)
      • Fireye Burner Control
      • First Time Start-Up
      • Daily Operations
      • End-of-Season Shut-Down
      • Suggested Operating Setpoints
    • Maintenance
      • Pre-Season Checks
      • Lubrication Schedule
      • Seasonal Cleaning
      • Post-Season Maintenance
    • Troubleshooting
      • Diagnosing a Dryer Shutdown
      • Diagnosing Safety Circuit via HMI
      • Diagnosing the Safety Circuit Using a Voltmeter
      • Emergency Stops
      • Customer Interface
      • Variable Frequency Drives
      • Soft Starters
      • Common Diagnostic Issues
Powered by GitBook
On this page
  • Applicable Models
  • Applicable Voltages
  • Parameters
  • Motor Data
  • Standard AI
  • Start / Stop / Direction
  • Start / Stop Mode
  • Frequency Reference Chain
  • Limits
  • Panel Display
Export as PDF
  1. Dryer Operations
  2. Operating Procedures
  3. VFD (Parameters)

Modular Towers (208/230/460V)

Applicable Models

  • 10' Modular Tower Models (10530 - 101375)

  • 12' Modular Tower Models (12-20-100 - 12-28-150)

The variable frequency drive controls the speed of the sweep arms for all tower dryers. The communication from the HMI to the PLC then correlates to the variable frequency drive. It is important to note that some of the parameters listed below will vary such as voltage, amperage and motor speed. These values should match the motor name plate.

Dip switches must both be set to ON for SIEMENS S7-1200.

If programmed by hand, upload to panel, then download full set to drive.

Applicable Voltages

  • 208V/3ph

  • 230V/3ph

  • 460V/3ph

  • 230V/1ph

Parameters

The following parameters apply to the dryer model(s) and voltage(s) as shown.

Motor Data

These parameters depend on machine voltage

Parameter
Description
MC Setting
Factory Default

99.04

Control Mode

Scalar-Freq

Scalar-Freq

99.06

Nominal Current

14.0 A (208V/3ph) 12.7 A (230V/3ph) 6.4 A (460V/3ph) 12.7 A (230V/1ph)

99.07

Nominal Voltage

208 V (208V/3ph) 230 V (230V/3ph) 460 V (460V/3ph) 230 V (230V/1ph)

99.08

Nominal Frequency

60 Hz

60 Hz

99.09

Nominal Speed

1725 RPM

99.10

Nominal Power

5 HP

Standard AI

Parameter
Description
MC Setting
Factory Default

12.15

Unit Selection

mA

V

12.17

AI1 Minimum

0.00

0

12.18

AI1 Maximum

20.00

10

12.19

AI1 Scaled at AI1 Min

0.00

0

12.20

AI1 Scaled at AI1 Max

60.00

60

Start / Stop / Direction

Parameter
Description
MC Setting
Factory Default

20.01

Ext 1 Commands

In1 Start

In1 Start; In2 Dir

20.04

Ext 1 in 2 Source

Always Off

DI2

20.11

Run Enable Stop Mode

Coast

Coast

20.12

Run Enable 1 Source

DI3

Selected

20.21

Direction

Forward

Request

Start / Stop Mode

Parameter
Description
MC Setting
Factory Default

21.01

Start Mode

Fast

Automatic

Frequency Reference Chain

Parameter
Description
MC Setting
Factory Default

28.22

Constant Freq Select 1

Always Off

DI3

28.23

Constant Freq Select 2

Always Off

DI4

28.71

Freq Ramp Set Select

Acc / Dec Time 1

DI5

28.72

Freq Acc Time

3.00

20

28.73

Freq Dec Time

3.00

20

Limits

These parameters depend on machine voltage

Parameter
Description
MC Setting
Factory Default

30.13

Min Frequency

5.00

-60

30.14

Max Frequency

60.00

60

30.17

Max Current

17 A (208V/3ph) 13.5 A (230V/3ph) 7.8 A (460V/3ph) 13.5 A (230V/1ph)

Panel Display

Parameter
Description
MC Setting
Factory Default

Options

Edit Home View

DI Delayed Status

Torque

PreviousProfile & Mixed-Flow ModelsNextModular Towers (380/575V)