LogoLogo
Dryer Operations
Dryer Operations
  • Dryer Operations
    • Applicability
    • Introduction
    • Warranty
    • CSA 3.8 2021
    • Specifications
      • Delta Series
      • Fusion Series
      • ECO Series
      • Legacy Series
      • Modular Tower Series
      • Commercial Tower Series
    • Equipment Overview
      • Main Dryer Components
      • High Voltage Cabinet
      • Low Voltage Cabinet
      • Pinnacle 20|20 Remote Cabinet
      • Customer Equipment Cabinet
      • Burner Control Cabinet
      • Discharge Moisture Sampler
      • Gas Train
      • Burner
    • Operating Procedures
      • Component Adjustments
      • Air Pressure Switch
      • High Limit Switch
      • VFD (Parameters)
        • Profile & Mixed-Flow Models
        • Modular Towers (208/230/460V)
        • Modular Towers (380/575V)
        • Commercial Towers (208/230/460V)
      • Soft Start (Parameters)
      • Fireye Burner Control
      • First Time Start-Up
      • Daily Operations
      • End-of-Season Shut-Down
      • Suggested Operating Setpoints
    • Maintenance
      • Pre-Season Checks
      • Lubrication Schedule
      • Seasonal Cleaning
      • Post-Season Maintenance
    • Troubleshooting
      • Diagnosing a Dryer Shutdown
      • Diagnosing Safety Circuit via HMI
      • Diagnosing the Safety Circuit Using a Voltmeter
      • Emergency Stops
      • Customer Interface
      • Variable Frequency Drives
      • Soft Starters
      • Common Diagnostic Issues
Powered by GitBook
On this page
  • Applicable Models
  • Applicable Voltages
  • Parameters
  • Group 99 Start Up Data
  • Group 10 Start / Stop / Direction
  • Group 11 Reference Select
  • Group 12 Constant Speeds
  • Group 14 Relay Outputs
  • Group 15 Analogue Outputs
  • Group 16 System Controls
  • Group 20 Limits
  • Group 34 Panel Display
Export as PDF
  1. Dryer Operations
  2. Operating Procedures
  3. VFD (Parameters)

Modular Towers (380/575V)

Applicable Models

  • 10' Modular Tower Models (10530 - 101375)

  • 12' Modular Tower Models (12-20-100 - 12-28-150)

The variable frequency drive controls speed of the sweep arms for all tower dryers. The communication from the HMI to the PLC then correlates to the variable frequency drive. It is important to note that some of the parameters listed below will vary such as voltage, amperage and motor speed. These values should match the motor name plate.

Dip switches must both be set to ON for SIEMENS S7-1200.

If programmed by hand, upload to panel, then download full set to drive.

Applicable Voltages

  • 380V/3ph/50Hz

  • 575V/3ph/60Hz

Parameters

The following parameters apply to the dryer model(s) and voltage(s) as shown.

Group 99 Start Up Data

These parameters depend on machine voltage

Parameter
Description
MC Setting
Factory Default

9901

Language

English

English

9902

Applied Macro

ABB Standard

None

9904

Motor Control Mode

Scalar-Freq (380V) Vector-Speed (575V)

Scalar-Freq

9905

Motor Nominal Voltage

380 V (380V) 575 V (575V)

NA

9906

Motor Nominal Current

8 A (380V) 5.2 A (575V)

NA

9907

Motor Nominal Freq

50 Hz (380V) 60 Hz (575V)

60.0

9908

Motor Nominal Speed

1435 RPM (380V) 1760 RPM (575V)

1710

9909

Motor Nominal Power

5 HP

3 HP

Group 10 Start / Stop / Direction

Parameter
Description
MC Setting
Factory Default

1001

Ext 1 Command

Dl1

Dl1,2

1003

Direction

Forward

Request

Group 11 Reference Select

Parameter
Description
MC Setting
Factory Default

1104

Reference 1 Minimum

0 Hz (380V) 0 rpm (575V)

0 Hz

1105

Reference 1 Maximum

60 Hz (380V) 1760 rpm (575V)

60 Hz

Group 12 Constant Speeds

Parameter
Description
MC Setting
Factory Default

1201

Constant Speed Select

Dl4,5

Dl3,4

Group 14 Relay Outputs

Parameter
Description
MC Setting
Factory Default

1407

RO 2 Off Delay

30 Sec

0 Sec

Group 15 Analogue Outputs

Parameter
Description
MC Setting
Factory Default

1501

A01 Content Select

Ext Ref 1

Output Freq

Group 16 System Controls

Parameter
Description
MC Setting
Factory Default

1601

Run Enable

Dl3

NOT SEL

Group 20 Limits

These parameters depend on machine voltage

Parameter
Description
MC Setting
Factory Default

2001

Minimum Speed

0 Hz (380V) 0 rpm (575V)

0 Hz

2002

Maximum Speed

60 Hz (380V) 1760 rpm (575V)

60 Hz

2003

Max Current

9.2 A (380V) 6.5 A (575V)

8.5 A

2007

Minimum Freq

0 Hz

0.0 Hz

2008

Maximum Freq

60 Hz (380V) 1760 rpm (575V)

60.0 Hz

Group 34 Panel Display

Parameter
Description
MC Setting
Factory Default

3415

Signal 3 Parameters

Dl1-3 Status

Torque