ID | Name | Type | Cause |
---|---|---|---|
ID | Name | Type | Cause |
---|---|---|---|
ID | Name | Type | Cause |
---|---|---|---|
ID | Name | Type | Cause |
---|---|---|---|
2
Linear Limit Fire Alarm
C
Linear Limits Circuit is Open - One of the LLC switches has opened due to high temperature.
3
High Gas Pressure Fault
C
High gas pressure detected in the gas train.
4
Emergency Stop Depressed
C
Emergency Stop depressed.
10
Motor Overload(s)
C
Overload has been detected for one of the motors, check the motor circuit protector or soft starter if equipped.
11
Blowers Tri-Start Auxiliary
A
One of the two contactors A or B has experienced a fault condition.
16
Grain Fill Timeout
B
Infeed grain fill is insufficient to maintain grain level.
24
Low Gas Pressure
B
Low gas/fuel pressure detected in the gas/fuel train.
26
Discharge Level
B
The discharge level switch is open due to a possible overload of grain or a blocked discharge takeaway system.
27
Customer Takeaway Fault
B
The customer takeaway equipment has failed or is not on, check customer takeaway equipment status contacts.
28
Discharge Jam - Proximity Switch
B
The Discharge metering system has possibly stopped running because the proximity sensor is not detecting rotation.
35
Mid Grain Band
A
The mid-grain temperature has exceeded or dropped below the mid-grain band alarm setpoint for a duration of 30 seconds.
36
Mid-Grain Band Delay
B
The mid-grain temperature has exceeded or dropped below the mid-grain band alarm setpoint for the duration of the mid-grain band delay.
37
Mid-Grain Temperature Probe 1
A
Mid-grain temperature probe #1 has failed or become disconnected.
38
Mid-Grain Temperature Probe 2
A
Mid-grain temperature probe #2 has failed or become disconnected.
49
Plenum Door(s)
C
An open plenum door has been detected with the control power on.
50
Customer E-Stop
C
Customer E-Stop Activated.
51
Plenum 1 Low Temperature
B
The temperature in plenum #1 has dropped below the low temperature setpoint.
52
Plenum 2 Low Temperature
B
The temperature in plenum #2 has dropped below the low temperature setpoint.
53
Plenum 3 Low Temperature
B
The temperature in plenum #3 has dropped below the low temperature setpoint.
54
Plenum 4 Low Temperature
B
The temperature in plenum #4 has dropped below the low temperature setpoint.
55
Plenum 5 Low Temperature
B
The temperature in plenum #5 has dropped below the low temperature setpoint.
56
Plenum 6 Low Temperature
B
The temperature in plenum #6 has dropped below the low temperature setpoint.
57
Plenum 7 Low Temperature
B
The temperature in plenum #7 has dropped below the low temperature setpoint.
58
Plenum 8 Low Temperature
B
The temperature in plenum #8 has dropped below the low temperature setpoint.
61
Plenum 1 High Temperature
C
The temperature in plenum #1 has exceeded the high temperature setpoint.
62
Plenum 2 High Temperature
C
The temperature in plenum #2 has exceeded the high temperature setpoint.
63
Plenum 3 High Temperature
C
The temperature in plenum #3 has exceeded the high temperature setpoint.
64
Plenum 4 High Temperature
C
The temperature in plenum #4 has exceeded the high temperature setpoint.
65
Plenum 5 High Temperature
C
The temperature in plenum #5 has exceeded the high temperature setpoint.
66
Plenum 6 High Temperature
C
The temperature in plenum #6 has exceeded the high temperature setpoint.
67
Plenum 7 High Temperature
C
The temperature in plenum #7 has exceeded the high temperature setpoint.
68
Plenum 8 High Temperature
C
The temperature in plenum #8 has exceeded the high temperature setpoint.
75
Infeed Moisture Sensor Signal Missing
A
The infeed sensor signal has dropped to below 0.5VDC and is probably disconnected.
76
Infeed Moisture Sensor Signal Too High
A
The infeed sensor signal has exceeded 9.5VDC and is probably too wet or faulty.
77
Discharge Moisture Sensor Signal Missing
A
The discharge sensor signal has dropped to below 0.5VDC and is probably disconnected.
78
Discharge Moisture Sensor Signal Too High
A
The discharge sensor signal has exceeded 9.5VDC and is probably too wet or faulty.
79
Fill 1 Equipment Fault
B
Fill 1 Equipment Status signal failed to close after signal to operate fill equipment.
80
Fill 2 (Cleanout) Equipment Fault
B
Fill 2 Equipment Status signal (Level Auger) Failed to close after signal to operate fill cleanout equipment.
100
Dryer Master Communications
A
The Dryer Master system board is not responding; check: (A) - Dryer Master board not powered up; (B) - Communications between PLC and Dryer Master board; (C) - Dryer Master software stopped.
111
High Discharge Moisture
A
The system has experienced high discharge moisture.
113
High Discharge Temperature
A
The system has experienced high discharge temperature.
114
Critical High Discharge Temperature
B
The system has experienced critical high discharge temperature.
115
Low Discharge Moisture
A
The system has experienced low discharge moisture.
116
Critical Low Discharge Moisture
B
The system has experienced critical low discharge moisture.
117
Low Discharge Temperature
A
The system has experienced low discharge temperature.
118
Critical Low Discharge Temperature
B
The system has experienced critical low discharge temperature.
121
High Infeed Moisture
A
The system has experienced high infeed moisture.
122
Critical High Infeed Moisture
B
The system has experienced critical high infeed moisture.
123
High Infeed Temperature
A
The system has experienced high infeed temperature.
124
Critical High Infeed Temperature
B
The system has experienced critical high infeed temperature.
125
Low Infeed Moisture
A
The system has experienced low infeed moisture.
126
Critical Low Infeed Moisture
B
The system has experienced critical low infeed moisture.
127
Low Infeed Temperature
A
The system has experienced low infeed temperature.
128
Critical Low Infeed Temperature
B
The system has experienced critical low infeed temperature.
131
High Plenum Temperature
A
The system has experienced high plenum temperature.
132
Critical High Plenum Temperature
B
The system has experienced critical high plenum temperature.
133
Low Plenum Temperature
A
The system has experienced low plenum temperature.
134
Critical Low Plenum Temperature
A
The system has experienced critical low plenum temperature.
135
AccuDry Suspended
B
The system is suspended due to: a. Rate out of range, b. Moisture sensor signal missing, or c. Drying temperature out of range.
141
High Discharge Speed
A
The system has experienced high discharge speed.
142
Critical High Discharge Speed
B
The system has experienced critical high discharge speed.
143
Low Discharge Speed
A
The system has experienced low discharge speed.
144
Critical Low Discharge Speed
B
The system has experienced critical low discharge speed.
145
Plenum 1 High Limit Switch
C
Burner #1 high temperature switch has been activated.
146
Plenum 2 High Limit Switch
C
Burner #2 high temperature switch has been activated.
147
Plenum 3 High Limit Switch
C
Burner #3 high temperature switch has been activated.
148
Plenum 4 High Limit Switch
C
Burner #4 high temperature switch has been activated.
149
Plenum 5 High Limit Switch
C
Burner #5 high temperature switch has been activated.
150
Plenum 6 High Limit Switch
C
Burner #6 high temperature switch has been activated.
151
Plenum 7 High Limit Switch
C
Burner #7 high temperature switch has been activated.
152
Plenum 8 High Limit Switch
C
Burner #8 high temperature switch has been activated.
153
Blower 1 Motor Starter
A
Blower #1 motor starter has experienced a fault condition.
154
Blower 2 Motor Starter
A
Blower #2 motor starter has experienced a fault condition.
155
Blower 3 Motor Starter
A
Blower #3 motor starter has experienced a fault condition.
156
Blower 4 Motor Starter
A
Blower #4 motor starter has experienced a fault condition.
157
Blower 5 Motor Starter
A
Blower #5 motor starter has experienced a fault condition.
158
Blower 6 Motor Starter
A
Blower #6 motor starter has experienced a fault condition.
159
Blower 7 Motor Starter
A
Blower #7 motor starter has experienced a fault condition.
160
Blower 8 Motor Starter
A
Blower #8 motor starter has experienced a fault condition.
161
Blower 1 Air Pressure
B
Blower #1 is not providing adequate pressure for burner operation.
162
Blower 2 Air Pressure
B
Blower #2 is not providing adequate pressure for burner operation.
163
Blower 3 Air Pressure
B
Blower #3 is not providing adequate pressure for burner operation.
164
Blower 4 Air Pressure
B
Blower #4 is not providing adequate pressure for burner operation.
165
Blower 5 Air Pressure
B
Blower #5 is not providing adequate pressure for burner operation.
166
Blower 6 Air Pressure
B
Blower #6 is not providing adequate pressure for burner operation.
167
Blower 7 Air Pressure
B
Blower #7 is not providing adequate pressure for burner operation.
168
Blower 8 Air Pressure
B
Blower #8 is not providing adequate pressure for burner operation.
169
Blower 1 Air Pressure Switch
A
Blower #1 air pressure switch is indicating air pressure when the blower is not operating.
170
Blower 2 Air Pressure Switch
A
Blower #2 air pressure switch is indicating air pressure when the blower is not operating.
171
Blower 3 Air Pressure Switch
A
Blower #3 air pressure switch is indicating air pressure when the blower is not operating.
172
Blower 4 Air Pressure Switch
A
Blower #4 air pressure switch is indicating air pressure when the blower is not operating.
173
Blower 5 Air Pressure Switch
A
Blower #5 air pressure switch is indicating air pressure when the blower is not operating.
174
Blower 6 Air Pressure Switch
A
Blower #6 air pressure switch is indicating air pressure when the blower is not operating.
175
Blower 7 Air Pressure Switch
A
Blower #7 air pressure switch is indicating air pressure when the blower is not operating.
176
Blower 8 Air Pressure Switch
A
Blower #8 air pressure switch is indicating air pressure when the blower is not operating.
177
Burner 1 Ignition Failure
A
Burner #1 has not been able to maintan an adequate flame signal for dryer operation.
178
Burner 2 Ignition Failure
A
Burner #2 has not been able to maintan an adequate flame signal for dryer operation.
179
Burner 3 Ignition Failure
A
Burner #3 has not been able to maintan an adequate flame signal for dryer operation.
180
Burner 4 Ignition Failure
A
Burner #4 has not been able to maintan an adequate flame signal for dryer operation.
181
Burner 5 Ignition Failure
A
Burner #5 has not been able to maintan an adequate flame signal for dryer operation.
182
Burner 6 Ignition Failure
A
Burner #6 has not been able to maintan an adequate flame signal for dryer operation.
183
Burner 7 Ignition Failure
A
Burner #7 has not been able to maintan an adequate flame signal for dryer operation.
184
Burner 8 Ignition Failure
A
Burner #8 has not been able to maintan an adequate flame signal for dryer operation.
185
Burner 1 False Flame
C
The flame sensing system has detected the presence of a flame with burner #1 off.
186
Burner 2 False Flame
C
The flame sensing system has detected the presence of a flame with burner #2 off.
187
Burner 3 False Flame
C
The flame sensing system has detected the presence of a flame with burner #3 off.
188
Burner 4 False Flame
C
The flame sensing system has detected the presence of a flame with burner #4 off.
189
Burner 5 False Flame
C
The flame sensing system has detected the presence of a flame with burner #5 off.
201
Burner 1 Lost Flame
B
Burner #1 successfully ignited, but was unable to maintain a sufficient flame.
202
Burner 2 Lost Flame
B
Burner #2 successfully ignited, but was unable to maintain a sufficient flame.
203
Burner 3 Lost Flame
B
Burner #3 successfully ignited, but was unable to maintain a sufficient flame.
204
Burner 4 Lost Flame
B
Burner #4 successfully ignited, but was unable to maintain a sufficient flame.
205
Burner 5 Lost Flame
B
Burner #5 successfully ignited, but was unable to maintain a sufficient flame.
206
Burner 6 Lost Flame
B
Burner #6 successfully ignited, but was unable to maintain a sufficient flame.
207
Burner 7 Lost Flame
B
Burner #7 successfully ignited, but was unable to maintain a sufficient flame.
208
Burner 8 Lost Flame
B
Burner #8 successfully ignited, but was unable to maintain a sufficient flame.
217
Safety Relay Failure
C
The Safety Relay failed to latch. Check the safety relay circuit is complete.
218
Cool Down Stopped
B
Cooldown Mode stop via HMI pushbutton.