The variable frequency drive (VFD) controls the speed of the dryer's metering/sweep discha. The VFD's parameters depend on the type of dryer and the machine's voltage. Select from the options below:
The variable frequency drive (VFD) controls the speed of the dryer's metering/sweep discharge. The VFD's parameters depend on the type of dryer and the machine's voltage. Select from the options on the following pages:
18' Commercial Tower Models (3000 - 4800)
The variable frequency drive controls speed of the sweep arms for all tower dryers. The communication from the HMI to the PLC then correlates to the variable frequency drive. It is important to note that some of the parameters listed below will vary such as voltage, amperage and motor speed. These values should match the motor name plate.
Dip switches must both be set to ON for SIEMENS S7-1200.
If programmed by hand, upload to panel, then download full set to drive.
208V/3ph
230V/3ph
460V/3ph
The following parameters apply to the dryer model(s) and voltage(s) as shown.
These parameters depend on machine voltage
99.04
Control Mode
Scalar-Freq
Scalar-Freq
99.06
Nominal Current
6.5 A (208V/3ph) 6.0 A (230V/3ph) 3.0 A (460V/3ph)
99.07
Nominal Voltage
208 V (208V/3ph) 230 V (230V/3ph) 460 V (460V/3ph)
99.08
Nominal Frequency
60 Hz
60 Hz
99.09
Nominal Speed
1725 RPM
99.10
Nominal Power
2 HP
12.15
Unit Selection
mA
V
12.17
AI1 Minimum
0.00
0
12.18
AI1 Maximum
20.00
10
12.19
AI1 Scaled at AI1 Min
0.00
0
12.20
AI1 Scaled at AI1 Max
60.00
60
20.01
Ext 1 Commands
In1 Start
In1 Start; In2 Dir
20.04
Ext 1 in 2 Source
Always Off
DI2
20.11
Run Enable Stop Mode
Coast
Coast
20.12
Run Enable 1 Source
DI3
Selected
20.21
Direction
Forward
Request
21.01
Start Mode
Fast
Automatic
28.22
Constant Freq Select 1
Always Off
DI3
28.23
Constant Freq Select 2
Always Off
DI4
28.71
Freq Ramp Set Select
Acc / Dec Time 1
DI5
28.72
Freq Acc Time
3.00
20
28.73
Freq Dec Time
3.00
20
These parameters depend on machine voltage
30.13
Min Frequency
5.00
-60
30.14
Max Frequency
60.00
60
30.17
Max Current
8.5 A (208V/3ph) 8.0 A (230V/3ph) 4.5 A (460V/3ph)
Options
Edit Home View
DI Delayed Status
Torque
10' Modular Tower Models (10530 - 101375)
12' Modular Tower Models (12-20-100 - 12-28-150)
The variable frequency drive controls the speed of the sweep arms for all tower dryers. The communication from the HMI to the PLC then correlates to the variable frequency drive. It is important to note that some of the parameters listed below will vary such as voltage, amperage and motor speed. These values should match the motor name plate.
Dip switches must both be set to ON for SIEMENS S7-1200.
If programmed by hand, upload to panel, then download full set to drive.
208V/3ph
230V/3ph
460V/3ph
230V/1ph
The following parameters apply to the dryer model(s) and voltage(s) as shown.
These parameters depend on machine voltage
99.04
Control Mode
Scalar-Freq
Scalar-Freq
99.06
Nominal Current
14.0 A (208V/3ph) 12.7 A (230V/3ph) 6.4 A (460V/3ph) 12.7 A (230V/1ph)
99.07
Nominal Voltage
208 V (208V/3ph) 230 V (230V/3ph) 460 V (460V/3ph) 230 V (230V/1ph)
99.08
Nominal Frequency
60 Hz
60 Hz
99.09
Nominal Speed
1725 RPM
99.10
Nominal Power
5 HP
12.15
Unit Selection
mA
V
12.17
AI1 Minimum
0.00
0
12.18
AI1 Maximum
20.00
10
12.19
AI1 Scaled at AI1 Min
0.00
0
12.20
AI1 Scaled at AI1 Max
60.00
60
20.01
Ext 1 Commands
In1 Start
In1 Start; In2 Dir
20.04
Ext 1 in 2 Source
Always Off
DI2
20.11
Run Enable Stop Mode
Coast
Coast
20.12
Run Enable 1 Source
DI3
Selected
20.21
Direction
Forward
Request
21.01
Start Mode
Fast
Automatic
28.22
Constant Freq Select 1
Always Off
DI3
28.23
Constant Freq Select 2
Always Off
DI4
28.71
Freq Ramp Set Select
Acc / Dec Time 1
DI5
28.72
Freq Acc Time
3.00
20
28.73
Freq Dec Time
3.00
20
These parameters depend on machine voltage
30.13
Min Frequency
5.00
-60
30.14
Max Frequency
60.00
60
30.17
Max Current
17 A (208V/3ph) 13.5 A (230V/3ph) 7.8 A (460V/3ph) 13.5 A (230V/1ph)
Options
Edit Home View
DI Delayed Status
Torque
Delta Series Models (D600/D600h - D3200/D3200h)
Fusion Series Models (F320/F320x - F660/F660x)
ECO Series Models (E300/E300h - E700/E700h)
Legacy Series Models (L1000 - L6000)
The variable frequency drive controls the speed of the metering rolls for all profile and mixed-flow dryers. The communication from the HMI to the PLC then correlates to the variable frequency drive. It is important to note that some of the parameters listed below will vary such as voltage, amperage and motor speed. These values should match the motor name plate.
Dip switches must both be set to ON for SIEMENS S7-1200.
If programmed by hand, upload to panel, then download full set to drive.
The following parameters apply to the dryer model(s) and voltage(s) as shown.
9901
Language
English
English
9902
Applied macro
ABB Standard
ABB Standard
9904
Control Mode
Scalar-Freq
Scalar-Freq
9905
Nominal Voltage
Dryer Voltage
9906
Nominal Current
Nameplate FLA
9907
Nominal Frequency
60 Hz
60 Hz
9908
Nominal Speed
1700 RPM
Motor Nameplate
1001
EXT1 Commands
DI1,2
DI1
1002
EXT2 Commands
NOT SEL
DI1
1003
Direction
Request
Forward
1102
ECT1/EXT2 Select
EXT1
DI2
1103
Ref 1 Select
AI1
AI1
1104
Ref 1 MIN
0 Hz
0 Hz
1105
Ref 1 MAX
60 Hz
60 Hz
1106
Ref 2 Select
AI2
Keypad
1107
Ref 2 MIN
0%
0%
1108
Ref 2 MAX
100%
100%
1201
Const. Speed Select
DI3,4
NOT SEL
1401
Relay Output 1
Fault(-1)
Fault(-1)
1501
AO1 Content Sel
Output Freq
Ext Ref 1
1601
Run Enable
NOT SEL
DI3
2003
Max Current
FLA x SF
2007
Min Frequency
0 Hz
0 Hz
2008
Max Frequency
60 Hz
60 Hz
2102
Stop Function
Coast
Ramp
2110
Torque boost current
100%
200%
2202
Accel Time 1
5 sec
5 sec
2203
Decel Time 1
5 sec
5 sec
3415
Signal 3 Parameters
Torque
DI1-5
10' Modular Tower Models (10530 - 101375)
12' Modular Tower Models (12-20-100 - 12-28-150)
The variable frequency drive controls speed of the sweep arms for all tower dryers. The communication from the HMI to the PLC then correlates to the variable frequency drive. It is important to note that some of the parameters listed below will vary such as voltage, amperage and motor speed. These values should match the motor name plate.
Dip switches must both be set to ON for SIEMENS S7-1200.
If programmed by hand, upload to panel, then download full set to drive.
380V/3ph/50Hz
575V/3ph/60Hz
The following parameters apply to the dryer model(s) and voltage(s) as shown.
These parameters depend on machine voltage
9901
Language
English
English
9902
Applied Macro
ABB Standard
None
9904
Motor Control Mode
Scalar-Freq (380V) Vector-Speed (575V)
Scalar-Freq
9905
Motor Nominal Voltage
380 V (380V) 575 V (575V)
NA
9906
Motor Nominal Current
8 A (380V) 5.2 A (575V)
NA
9907
Motor Nominal Freq
50 Hz (380V) 60 Hz (575V)
60.0
9908
Motor Nominal Speed
1435 RPM (380V) 1760 RPM (575V)
1710
9909
Motor Nominal Power
5 HP
3 HP
1001
Ext 1 Command
Dl1
Dl1,2
1003
Direction
Forward
Request
1104
Reference 1 Minimum
0 Hz (380V) 0 rpm (575V)
0 Hz
1105
Reference 1 Maximum
60 Hz (380V) 1760 rpm (575V)
60 Hz
1201
Constant Speed Select
Dl4,5
Dl3,4
1407
RO 2 Off Delay
30 Sec
0 Sec
1501
A01 Content Select
Ext Ref 1
Output Freq
1601
Run Enable
Dl3
NOT SEL
These parameters depend on machine voltage
2001
Minimum Speed
0 Hz (380V) 0 rpm (575V)
0 Hz
2002
Maximum Speed
60 Hz (380V) 1760 rpm (575V)
60 Hz
2003
Max Current
9.2 A (380V) 6.5 A (575V)
8.5 A
2007
Minimum Freq
0 Hz
0.0 Hz
2008
Maximum Freq
60 Hz (380V) 1760 rpm (575V)
60.0 Hz
3415
Signal 3 Parameters
Dl1-3 Status
Torque